Technical Specifications
-
SUN-7K-G02P1-EU-AM2
-
SUN-7.5K-G02P1-EU-AM2
-
SUN-8K-G02P1-EU-AM2
- Feedback
| Model | SUN-7K-G02P1-EU-AM2 | SUN-7.5K-G02P1-EU-AM2 | SUN-8K-G02P1-EU-AM2 |
|
PV String Input Data
|
|||
|
Max. PV Input Power (kW)
|
10.5 | 11.3 | 12 |
|
Max. PV Input Voltage (V)
|
550 | ||
|
Start-up Voltage (V)
|
80 | ||
| MPPT Voltage Range (V) | 70-500 | ||
| Rated PV Input Voltage (V) | 360 | ||
| Max. Operating PV Input Current (A) | 18+26 | ||
| Max. Input Short Circuit Current (A) | 27+39 | ||
| No. of MPP Trackers/No. of Strings per MPP Tracker | 2/1+2 | ||
|
AC Output Side
|
|||
| Rated AC Output Active Power (kW) | 7 | 7.5 | 8 |
| Max. AC Output Apparent Power (kVA) | 7.7 | 8.25 | 8.8 |
| Rated AC Output Current (A) | 31.9/30.5 | 34.1/32.7 | 36.4/34.8 |
| Max. AC Output Current (A) | 35/33.5 | 37.5/35.9 | 40/38.3 |
| Rated Output Voltage/Range (V) | 220/230 0.85Un-1.1Un | ||
| Grid Connection Form | L/N/PE | ||
| Rated Output Grid Frequency/Range(Hz) | 50/45-55, 60/55-65 | ||
| Power Factor Adjustment Range | 0.8 leading to 0.8 lagging | ||
| Total Current Harmonic Distortion THDi | <3% | ||
| DC Injection Current | <0.5% | ||
| Efficiency | |||
| Max.Efficiency | 97.70% | ||
| Euro Efficiency | 97.20% | ||
| MPPT Efficiency | >99% | ||
|
Equipment Protection
|
|||
| DC Polarity Reverse Connection Protection | Yes | ||
| AC Output Overcurrent Protection | Yes | ||
| AC Output Overvoltage Protection | Yes | ||
| AC Output Short Circuit Protection | Yes | ||
| Thermal Protection | Yes | ||
| DC Terminal Insulation Impedance Monitoring | Yes | ||
| DC Component Monitoring | Yes | ||
| Ground Fault Current Monitoring | Yes | ||
|
Arc Fault Circuit Interrupter (AFCI)
|
Optional
|
||
| Power Network Monitoring | Yes | ||
| Island Protection Monitoring | Yes | ||
| Earth Fault Detection | Yes | ||
| Overvoltage Load Drop Protection | Yes | ||
| Residual Current (RCD) Detection | Yes | ||
| Surge Protection Level | TYPE II(DC), TYPE II(AC) | ||
| Interface | |||
| Communication Interface | RS485/RS232 | ||
|
Monitor Mode
|
GPRS/WIFI/Bluetooth/4G/LAN(optional)
|
||
| General Data | |||
| Operating Temperature Range (°C) |
-25 to +60℃, >45℃ Derating
|
||
| Permissible Ambient Humidity | 0-100% | ||
| Permissible Altitude (m) | 3000m | ||
| Noise (dB) | ≤35 | ||
| Ingress Protection(IP) Rating | IP 65 | ||
| Inverter Topology | Non-Isolated | ||
| Over Voltage Category | OVC II(DC), OVC III(AC) | ||
| Cabinet Size (WxHxD mm) | 330×310×208.5(Excluding Connectors and Brackets) | ||
| Weight (kg) | 12.1 | ||
| Warranty | 5years | ||
| Type of Cooling | Natural Cooling | ||
| Grid Regulation | IEC 61727, IEC 62116, EN 50549, NRS 097, RD 140, UNE 217002, G99 | ||
| Safety EMC/Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 | ||